Descripción
HT Instruments HT9022 Clamp-On Power Quality Analyzer with Bluetooth Connection
Manufacturer Specs
| HT Instruments HT9022 Technical Specifications | |
| Accuracy is calculated as [% rdg + (number of dgt) x resolution]. It is referred to 23°C ± 5°C, <80%RH | |
| ELECTRICAL SPECIFICATIONS | |
| DC Voltage | 0.5 ÷ 99.9V |
| (AC+DC) TRMS Voltage | 0.5 ÷ 999.9V |
| AC/DC Voltage – MAX/MIN/CREST | 0.5 ÷ 999.9V |
| DC Current | 0.5 ÷ 999.9A |
| AC (AC+DC) TRMS Current | 0.5 ÷ 999.9A |
| AC/DC Current – MAX/MIN/CREST | 0.5 ÷ 999.9A |
| Resistance and Continuity test | 0.0Ω ÷ 59.9kΩ |
| Frequency with test leads and jaws | -10.0 ÷ 99.9Hz – 100 ÷ 400Hz |
| DC Power | 0.00 ÷ 99.99kW – 100.0 ÷ 999.9kW |
| Active, Reactive, Apparent Power | 0.00 ÷ 99.99 – 100.0 ÷ 999.9 [kW, kVAR, KVA] |
| Active, Reactive Energy | 0.00 ÷ 99.99 – 100.0 ÷ 999.9 [kWh, kVARh] |
| Power Factor | 0.20 ÷ 1.00 |
| GENERAL SPECIFICATIONS | |
| Characteristics of radio module | |
| Radio | Bluetooth V2.0 |
| Frequency | 2.4 GHz (2400-2483.5MHz) |
| Power | Class 2 |
| Data rate | 57600 baud |
| Memory | |
| Internal memory | 2Mbytes |
| Recordings | |
| N°. max Log + Snapshot stores | 99 |
| N°. max InRush stores | 20 (each with max 10 events) |
| Mechanical characteristics | |
| Dimensions (L x W x H) | 252 (L) x 88 (W) x 44 (H) mm; 9.92 x 3.46 x 1.73 in |
| Weight (including battery) | approx 420g; 14.8 ounces |
| Max conductor size | 45mm; 1.77 in |
| Power Supply | |
| Battery type | 2 batteries x 1.5V LR 03 AAA |
| Battery life | approx. 53 hours of use in “W ” position |
| Auto power OFF | 5 min. with enabled function The display shows the following symbol |
| Display | |
| Characteristics | graphic display 128×128 pixels |
| Updating frequency | 128 samples per period (base sampling) |
| Conversion mode | 1/s |
| Climatic conditions | |
| Reference calibration temperature | 23° ± 5 °C |
| Operating temperature | 0 ÷ 40 °C |
| Allowable relative humidity | < 80% |
| Storage temperature | -20 ÷ 60 °C (-4°F ÷ 140°F) |
| Storage humidity | -10 ÷ 60 °C |
| Safety Standards | |
| Compliant with Standards | IEC / EN61010-1, IEC / EN61010-2 – 032 |
| Technical documentation | IEC/EN61187 |
| Safety of measuring accessories | IEC/EN61010-31 |
| Insulation | Class 2, double insulation |
| Insulation | Class 2, double insulation |
| Pollution level | 2 |
| Max height | 2000m, indoor use |
| Overvoltage category | CAT IV 600V / CAT III 1000V to earth, max 1000V between inputs |
Tech Specs
Clamp Meters/Clamp Meters Template |
|
|---|---|
| True RMS | Yes |
| Maximum Current AC | 1000 A |
| Maximum Current DC | 1000 A |
| Maximum Voltage AC | 1000 V |
| Maximum Voltage DC | 1000 V |
| Maximum Conductor Size | 45 MM (1.77 IN) |
| Resistance | Yes |
| Capacitance | No |
| Auto Ranging/Manual | Auto Ranging |
| In-Rush Current | Yes |
Test Equipment General Attributes |
|
| Unique Features | Full Power Quality Analysis Bluetooth Connectivity to Andriod Devices Harmonics up to 25th harmonic |
| Safety Approval | CE |
| Product Weight | 420 GRAMS (0.926 LBS) |
| Product Height | 44 MM (1.73 IN) |
| Product Length | 252 MM (9.92 IN) |
| Data Logging | Yes |
| HTS/Schedule B Number | 90303330 |
| ECCN Number | EAR99 |
| Calibration Included | Factory Calibration |
| Battery Type | AAA |
| Power Supply Voltage | Battery Powered |
| Country of Origin | China |










Valoraciones
No hay valoraciones aún.