Descripción
Comet H3431 Temperature and Humidity Regulator with RS485 Output

- H3431 Temperature and Humidity Regulator with RS485 Output
- Equipped with two relay outputs for alarm indication or control of external devices
- Parameters are easy adjustable from regulator keyboard or from the computer
- Large dual line LCD for simultaneous display of temperature
- State-of-the-art capacitive polymer sensor ensures excellent calibration long term stability
Humidistat, thermostat with two relay outputs. Outdoor, indoor use.
Relative humidity, temperature probe on a cable. Measured values are also converted to other humidity interpretation: dew point temperature, absolute humidity, specific humidity, mixing ratio, specific enthalpy. Three two-state inputs.
The device is supplied with T+RH probe with 1m cable. Cable lengths 2m or 4m available optionally.
Humidistat is designed for two-state control of e.g. heating, ventilation, humidifier, dehumidifier, etc.
Transmitter is equipped with two relay outputs for alarm indication or control of external devices. Each relay can be assigned to any measured or computed value. For each relay setting of delay, hysteresis, audible alarm is enabled.
Measured temperature and relative humidity is recalculated to other humidity interpretations – dew point temperature, absolute humidity, specific humidity, mixing ratio or specific enthalpy.
Parameters are easy adjustable from regulator keyboard or from the computer. Large dual line LCD for simultaneous display of temperature, relative humidity or other calculated humidity interpretation is an advantage.
State-of-the-art capacitive polymer sensor ensures excellent calibration long term stability, inertia against water and condensation. Transmitter is designed for use in non-aggressive environment.
Transmitter is also equipped with three binary inputs for detection of two-state events – e.g. water, smoke, glass break detection, door contact.
Applications
- temperature control
- monitoring of temperature and three binary signals at:
- building management and automation
- server rooms
- telecommunication devices
- warehouses, glasshouses
- manufacturers
- museums, archives, galleries
- air-conditioned rooms, HVAC
Software
- Comet Database
- Complex solution for data acquisition and analysing. Easy to use and high flexible database software for Comet Transmitters and Regulators.
- Sensor RS485/232 utility
- Allows communication of sensors with RS485/RS232 output and sending data to Comet Database.
- T-Sensor software
- Free configuration utility for Comet Transmitters and Regulators.
- SensorReader software
- Basic data acquisition utility for Comet Transmitters and Regulators. Software is free for download.
- Programmable regulators
- with RS485 galvanic isolated serial interface are designed to measure temperature, relative humidity and barometric pressure of air in non-aggressive environment, to alarm indication and to control of external devices. Three galvanic no isolated binary inputs are intended for detection of binary signals. Regulators are available in wall – mount, duct – mount versions or with probe on a cable. Type H3431P is designed for measurement the temperature and relative humidity of compressed air.
- The function of two output relays
- can be set from regulator keyboard (or from computer) and using the jumpers (see «Electrical wiring»). You can assign one of measured or computed value (dew point temperature, absolute humidity, specific humidity mixing ratio an d specific enthalpy) to ea ch relay. The s etting of delay, hysteresis and audible alarm is enabled for each relay. The status of output relays can be controlled remotely via RS485 link too. Devices are equipped with four button keyboard and two – line LCD display.
- Regulators support
- Modbus RTU protocol and protocol compatible with standard Advantech-ADAM.

Serial output RS485 is galvanically isolated from other circuitry to prevent collisions on the RS485 bus. The transmitter works with ModBus RTU communication protocol or with Advantech ADAM compatible protocol. Protocol is user selectable in special configuration mode by means of the PC. Serial link enables to read actual readings and modify transmitter configuration. Instrument works always in slave mode, i.e. responds only to master device query. Transmitters have the address space available from 0 to 255. Communication speed is 110 to 115200Bd.
Manufacturer Specs
| Technical Parameters | Value |
| Output | RS485 |
| Measured Value | Temperature + Relative Humidity |
| Construction Type | With T+RH Probe on Cable |
| Design | Industrial |
| Temperature Measuring Range | -30 to 105 °C |
| Relay Output | Yes |
| Two-State Input | Yes |
| Lcd Display | Yes |
| PoE | No |
| Maximum switching voltage, current, power of relay output | 50V, 2A, 60VA |
| Audible alarm | from built-in beeper – switchable |
| Relative humidity range | 0 to 100% |
| Accuracy of relative humidity measurement | ±2.5% relative humidity from 5 to 95% at 23°C |
| Accuracy of temperature output | ±0.4°C from -30 to +100°C ±0.4% from reading over +100°C |
| Available temperature units | degrees Celsius, Fahrenheit |
| Accuracy and range of dew point temperature output – for more details see graphs | ±1.5°C at ambient temperature T<25°C and RH>30% range -60 to +80 °C |
| Accuracy and range of absolute humidity output | ±1.5g/m3 at ambient temperature T < 25°C range 0 to 400 g/m3 |
| Accuracy and range of specific humidity output | ±2g/kg at ambient temperature T < 35°C range 0 to 550 g/kg |
| Accuracy and range of mixing ratio output | ±2g/kg at ambient temperature T < 35°C range 0 to 995 g/kg |
| Accuracy and range of specific enthalpy output | ±3kJ/kg at ambient temperature T < 25°C range: 0 to 995 kJ/kg |
| Signal for binary inputs | from voltage-less contact, open collector or two-state voltage signal. Inputs are not galvanically isolated. |
| Minimum pulse length at binary input | 500 ms |
| Voltage at open contact | 3.3 V |
| Low voltage level | 0 to +0.5 V |
| High voltage level | +3.0 to +30V |
| Temperature operating range | -30 to +80°C |
| Temperature operating range of LCD display | readable to operating temperature +70°C, it is recommended to switch OFF the LCD over +70°C |
| Temperature compensation of the humidity sensor | all temperature range |
| Filtering ability of sensor cover | 0.025mm – filter with stainless steel mesh |
| Communication protocol | ModBus RTU and Advantech ADAM compatible protocol |
| Communication speed | 110 to 115200 Bd |
| IP protection | IP65 electronics, IP40 sensors |
| Power | 9-30Vdc, power consumption approximately 1W |
| Length of the probe cable | 1m, 2m or 4m optionally |
| Dimensions | 136 x 159 x 45 mm (W x H x D), probe length 88 mm, probe diameter 18mm |
| Weight | approximately 420g – 1m probe |
| Warranty | 3 years |
Tech Specs
Test Equipment General Attributes |
|
|---|---|
| Product Weight | 1 LBS |
| Shipping Weight | 1.15 LBS |
| Country of Origin | Czech Republic |




Valoraciones
No hay valoraciones aún.